HDT1 Series Isolating Switch | |
|
HDT1 Series Isolating Switch
|
|
|
Application
|
|
Applying to making and breaking power turn-circuit of voltage 415V, frequency 50-60Hz,rated current less than 250A,acting as power switch, isolating switch and emergency switch. Because of special system of arc-contact and main- contact,HDT1 operates with high efficiency,safety and reliability, conforming to 415V(AC-23) and IEC947/3. GB14048.3 standard. Rotational operation and direct mechanical connection between handle and moving contact, on-off handle makes contact break and indicating place of contact. Panel and independent type installation are 铿乼ted with HDT1.
|
|
Technical parameter conform to IEC947-3銆丟B14048.3
|
|
Specification
|
63
|
125 |
160 |
250 |
250 |
630 |
Number of main poles
|
4 |
4 |
4 |
4 |
4 |
4 |
Rated insulation voltage V~
|
690
|
690
|
800
|
800
|
1000
|
1000
|
Rated operational voltage V~
|
415
|
415
|
415
|
415
|
415
|
415
|
Rated operational current A
|
63
|
125
|
160
|
250
|
400
|
630
|
Rated thermal current A
|
63
|
125
|
200
|
250
|
400
|
630
|
Rated short-circuit withstand current 1sec KA
|
3 |
5 |
10
|
10
|
17
|
25
|
Rated cirxuit making capacity KA
|
4.8
|
8
|
15
|
15
|
32
|
50
|
Rated linutubg short-circuit current KA
|
100
|
100
|
100
|
100
|
100
|
100
|
Operating
capbility
|
Mechanical
enduranced
|
Operations
|
8500
|
8500
|
7000
|
7000
|
4000
|
4000
|
Elecrtic
enduranced
|
Operations
|
1500
|
1500
|
1000
|
1000
|
1000
|
1000
|
Weight Kg
|
0.5
|
1.0
|
2.05
|
2.2
|
3.5
|
6.0
|
Rated making and breaking capacity
AC-23 Cos 桅=0.35
|
The rated current of making 10 time
and braking 8 times
|
Auxiliary Switch (380V AC-15) A
|
16 |
|
|
|
|
|